Products  
Products Product Details
Product name: WSL, WDL
Listing Date:2017-07-30

Type WSL De-Energized Tap Changer (herein referred as tap changer) is of in-tank structure and without separate oil compartment. It is mounted to transformer tank by a tap changer head ange.

By the operation method, tap changer can be divided into motor driving at man position, and manual drive mechanism operating at man position as well as hand wheel manual operation on the top. 


Item

Specification

WSL, WDL

1

Max. rated through-current (A)

600

800

1000

1200

1600

2000

2400

3000


Short-circuit

current test (kA)

Thermal (3s)

9

12

15

15

20

24

26

30

Dynamic (Peak)

22.5

30

37.5

37.5

50

60

65

75

 2

Rated frequency (Hz)

50 or 60

3

Connection

3 phases (WSL), single phase (WDL)

7

Max. Operating Positions

Max. 5 for types A and B, max. 11 for type D and max. 17 for type E

8

Insulation

to ground

(kV)

Highest voltage for

equipment Um

12

72.5

126

145

170

252

Rated separate source AC

withstand voltage (kV/50Hz,1min)

35

140

230

275

325

460

Rated lightning impulse

withstand voltage (kV,1.2/50μs)

75

325

550

650

750

1050

9

Contact circle diameter

Type A: ⌀350; type B: ⌀500; type D: ⌀600; type E: ⌀750

10

Mechanical life

Not less than 20,000 operations for manual driving

Not less than 100,000 operations for motor driving

13

Motor drive unit

SHM-D or CMA7


Related Products
/ Case More>>
2017 - 07 - 30
Clicks:
2017 - 08 - 01
Clicks:
2016 - 07 - 31
Clicks:
Copyright © 2005 - 2013 Shanghai Huaming Power Equipment
犀牛云提供企业云服务
Address: No.977, Tongpu Road, Shanghai, 200333, China 
Tel: 86 21 5270 8966
E-mail: export@huaming.com